Summary

A positive pressure container maintains higher air pressure inside than in a defined adjacent space. That difference drives air outward through leakage paths, helping limit ingress of airborne contaminants when the ventilation system is operating as designed.


How Positive Pressure Works

In a typical mechanically ventilated module, a fan supplies air from a suitable clean source. The system delivers more air than it removes through mechanical exhaust, and the excess leaves through relief openings and other leakage paths. The pressure difference depends on both the airflow balance and how easily air can escape through doors, seals and service penetrations. Recirculating air with a standard air conditioner can cool the room without creating the required pressure difference.


The pressure reading is relative to a defined reference, such as an adjoining corridor, an airlock or the surrounding atmosphere. A differential pressure sensor measures across that boundary. The design must account for conditions that can change the reading or the airflow direction, including doors opening, process extraction starting, filters loading and wind acting on an exposed module.


Where Positive Pressure Is Used

Offshore control rooms and electrical equipment shelters are common candidates when the principal airborne hazard is outside the module. A clean-air supply and outward airflow can help protect the interior from airborne dust or contaminants. Where the outside atmosphere can be explosive, the design needs a defined protection concept. Depending on that concept, it may require a purge before energization, pressure and airflow monitoring, alarms and specified actions if pressurization is lost. IEC 60079-13 on protection by pressurized and artificially ventilated rooms


Positive pressure can also carry contaminants generated inside a room toward neighboring spaces. The project hazard assessment should identify release sources on both sides of the boundary before the team selects the ventilation strategy and reviews the applicable codes. A module with internal extraction may need local capture or a pressure cascade between spaces.


What the Project Specification Should Define

  • Design conditions. Identify the external area classification where applicable, internal processes, occupancy, and the location of the clean-air source.
  • Ventilation and controls. Define the reference space, pressure and airflow criteria, extraction loads, door operating conditions, alarms, and the response to fan or power loss.
  • Acceptance and documentation. Agree how the team will verify pressure, airflow direction and alarm response. Where hazardous-area protection is required, check the documentation against the actual configuration and installation conditions.


Frequently Asked Questions

Does positive pressure mean the container is certified for a hazardous area?

A positive reading indicates a pressure difference at the measurement points. Hazardous-area suitability must be established for the specific protection concept, equipment, classification and installation conditions.


Is there a standard pressure setpoint for all containers?

The setpoint depends on the applicable requirements, the pressure reference, leakage paths, door operation and expected ventilation loads. The project should also define the minimum acceptable pressure and the conditions used to verify it.


Further Reading


Discuss Your Pressurized Container with TLS

Send TLS your project location, site classification, intended room use, available clean-air source, extraction loads and any required protection standard. Email TLS Offshore Containers