IEC 60079-13:2017 gives requirements for the design, construction, assessment, verification and marking of rooms used to protect internal equipment:
– located in a Zone 1 or Zone 2 or Zone 21 or Zone 22 explosive atmosphere without an internal source of gas/vapour release and protected by pressurization;
– located in a Zone 2 explosive atmosphere with or without an internal source of gas/vapour release and protected by artificial ventilation;
– located in a non-hazardous area, containing an internal source of gas/vapour release and protected by artificial ventilation;
– located in a Zone 1 or Zone 2 or Zone 21 or Zone 22 explosive atmosphere containing an internal source of gas/vapour release and protected by both pressurization and artificial ventilation.
The term "room" used in this document includes single rooms, multiple rooms, a complete building or a room contained within a building. A room is intended to facilitate the entry of personnel and includes inlet and outlet ducts. An acoustic hood and other like enclosures designed to permit the entry of personnel can be considered as a room.
This document also includes requirements related safety devices and controls necessary to ensure that artificial ventilation, purging and pressurization is established and maintained.
A room assembled or constructed on site, can be either on land or off-shore. The room is primarily intended for installation by an end-user but could be constructed and assessed at a manufacturer’s facility, where the final construction such as ducting can be completed on site.
This document does not specify the methods that may be required to ensure adequate air quality for personnel with regard to toxicity and temperature within the room. National or other regulations and requirements may  exist to ensure the safety of personnel in this regard.
This second edition cancels and replaces the first edition published in 2010. This edition constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous edition:
a) modification of the title of this document to include artificially ventilated room "v" in addition to pressurized room "p";
b) addition of types of protection "pb", "pc", and "vc" and removal of types of protection "px", "py", "pz" and "pv";
c) definition of the differences between pressurization and artificial ventilation types of protection;
d) removal of protection of rooms with an inert gas or a flammable gas from the scope of this document;
e) addition of an informative annex to include examples of applications where types of protection pressurization or artificial ventilation or pressurization and artificial ventilation can be used and associated guidelines.
The fire proof system can be divided into two aspects, these are passive and active protection.
Active fire protection - manual and automatic detection and suppression of fires,
For example:
Fire or smoke detector system
Fire alarm systems.
Fire sprinkler systems
Fire extinguisher
Firefighter
Passive fire protection (PFP) - The installation of fire rated walls, ceiling and floor assemblies to form fire compartments intended to limit the spread of fire, high temperatures, and smoke.
For example:
To improve fire resistance performance of material
To paint the fire-retardant coating, such as cementitious and epoxy intumescent.
To cover the insulated panel

Fire Testing
For PFP materials to be classified for offshore use they must meet three main fire-testing requirements that are commonly accepted. These are Standard fire test, Hydrocarbon pool fire test and Hydrocarbon jet fire test.
 
Fire proof classification according to Standard Fire test
There are three classification which are A, B and C class.
1. "A" class divisions:
1). They are constructed of steel or other equivalent material;
2). They are suitably stiffened;
3). They are constructed as to be capable of preventing the passage of smoke and flame to the end of the one-hour standard fire test;
4). They are insulated with approved non-combustible materials such that the average temperature of the unexposed side will not rise more than 140ºC above the original temperature, nor will the temperature, at any one point, including any joint, rise more than 180ºC above the original temperature, within the time listed below:
     Class "A-60”   60 min
     Class "A-30”   30 min
     Class "A-15”   15 min
     Class "A-0”      0 min
2. "B" class divisions:
1). They are constructed of approved non-combustible materials and all materials used in the construction and erection of "B" class divisions are non-combustible, with the exception that combustible veneers may be permitted provided they meet other appropriate requirements of this chapter;
2). They are constructed as to be capable of preventing the passage of flame to the end of the first half hour of the standard fire test;
3). They have an insulation value such that the average temperature of the unexposed side will not rise more than 140ºC above the original temperature, nor will the temperature at any one point, including any joint, rise more than 225ºC above the original temperature, within the time listed below:
     Class "B-15"    15 min
     Class "B-0"       0 min
3.  "C" class divisions 
Divisions constructed of approved noncombustible materials. They need meet neither requirements relative to the passage of smoke and flame nor limitations relative to the temperature rise.

Fire proof classification according to Hydrocarbon Pool Fire test
"H" class divisions:
1. They are constructed of steel or other equivalent material;
2. They are suitably stiffened;
3. They are constructed as to be capable of preventing the passage of smoke and flame to the end of the two-hour standard fire test;
4. They are insulated with approved non-combustible materials such that the average temperature of the unexposed side will not rise more than 140ºC above the original temperature, nor will the temperature, at any one point, including any joint, rise more than 180ºC above the original temperature, within the time listed below:
     Class "H-120”    120 min
     Class "H-60”       60 min
     Class "H-0”          0 min

Fire proof classification according to Hydrocarbon Jet Fire test
"J" class divisions:
1. They are constructed of steel or other equivalent material;
2. They are suitably stiffened;
3. They are constructed as to be capable of preventing the passage of smoke and flame to the end of the first half hour standard fire test;
4. They are insulated with approved non-combustible materials such that the average temperature of the unexposed side will not rise more than 140ºC above the original temperature, nor will the temperature, at any one point, including any joint, rise more than 180ºC above the original temperature, within the time listed below:
     Class "J-60”    60 min
     Class "J-30”    30 min
Image description





​