When the gas protection function is enabled, the high-pressure air would be depressed by depressurizing system and then fresh air would be supplied to the main room. A micro-positive pressure of 50pa would be kept in the main room and 25pa in the air-lock area. Due to the internal pressure in the temporary refuge shelter is slightly higher than the atmosphere pressure, the internal air will vent through the check valve and the hazardous gas will be blocked outside.

Control room of temporary refuge shelter, toxic gas refuge cabin

Fire ratings such as A60 and H120 indicate the duration the doors and walls must be able to withstand a particular type of fire. 
​
Difference between A- and H-fire ratings
A-fire rated doors and walls are tested with a ISO cellulosic fire temperature curve. H-fire rated items are tested with a hydrocarbon fire curve. The hydrocarbon fire curve has a faster build-up and higher plateau temperature than the standard A-curve. 
The fire doors and fire walls shall maintain their function with respect to fire resistance and structural integrity when exposed to a heat load characteristic for cellulosic (A-fire rating) fire or hydrocarbon (H-fire rating) fire.

A0, A60, H0, H60 AND H120 RATINGS
Temporary refuge shelter, Toxic gas refuge cabin, H2S refuge shelter

Temporary refuge shelter, Toxic gas refuge cabin, H2S refuge shelter

The toxic gas refuge design will comply to the following main features:
a)  The TGR must be designed for a H2S atmosphere.
b)  TGR is provide protection against fire for one hour.
c)  TGR will resist to external Heat Stress due to fire of inflammable gas. No internal Heat Stress has been
considered, due to the inflammable gas detectors installed onboard which will automatically shut down auxiliary systems and dampers of the System which could permit:
-  the circulation of gas inside the HVAC system.
-  fire igniting sparks (electric contacts not rated explosion proof).
d)  TGR will provide recovery to POB in case of detection of gas mix including at least: H2S and hydro-carbon Lower Explosion Limit (LEL) and Temporary smoke with particles suspension.
e)  TGR will allow to provide temporary medical assistance to injured personnel who cannot use standard means of survival.
f)  TGR will allow to provide temporary medical assistance to personnel hosted inside the hospital.
g)  The System shall be completely automatic.